1 Publication 1757-RN508A-EN-P - October 2003
Release Note
ProcessLogix R500.1 Service Pack 1
Introduction
This document describes the following:
contents of Service Pack 1 (SP1)
installation of this update
problems resolved in this update
known problems in this update
IMPORTANT
It is recommended that customers with event archiving licensed kick off an event
prior to installing this service pack.
Installation of this service pack requires shutting down Services on a non-redundant
ProcessLogix Server for the duration of the installation. Redundant Server databases
cannot be synchronized until this service pack has been installed on both SERVERB
and SERVERA. This will cause a loss of process view from all Stations, and a period of
no history or events from the system during installation. The gap in process data will
be approximately 45 minutes. On Redundant Servers, this gap can be partially offset
by archiving history just prior to the failover from the primary Server. If you have
questions about this gap or the implications of losing data during this installation,
contact Rockwell Automation Technical Support prior to installing this service pack.
During installation of this software update on the backup server, there will not be
access to the primary engineering database (ERDB). It will therefore be impossible to
perform Control Builder downloads during this time.
During installation of this software update on a non-redundant or primary server, the
following ProcessLogix Server features will not function:
Alarm/event reports
Event summary (filtered view)
ODBC Driver event table
Event archiving
It is recommended that customers with event archiving licensed change their periodic
archive time from midnight to 1 a.m so that archiving does not coincide with other
processing that occurs at midnight.
Zobrazit stránku 0
1 2 3 4 5 6 ... 14 15

Shrnutí obsahu

Strany 1 - Introduction

1 Publication 1757-RN508A-EN-P - October 2003Release NoteProcessLogix R500.1 Service Pack 1IntroductionThis document describes the following:• content

Strany 2 - Contents of R500.1 SP1

Publication 1757-RN508A-EN-P - October 200310 ProcessLogix R500.1 Service Pack 1 37883 Station The server TaskLRN is not sent immediately

Strany 3 - Server Installation

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 11Known Problems in R500.1 SP1This section lists known probl

Strany 4

Publication 1757-RN508A-EN-P - October 200312 ProcessLogix R500.1 Service Pack 1 39099 Backup Utility The utility creates points.bak on

Strany 5 - Client Installation

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 13Client35445 Migration Microsoft Excel Report configuratio

Strany 6 - Event Subsystem Updates

Publication 1757-RN508A-EN-P - October 200314 ProcessLogix R500.1 Service Pack 1 30583 DR 1-5IEWLStation Message box saying SafeBrowse ha

Strany 7 - Problems Resolved in

Publication 1757-RN508A-EN-P - October 2003 15 PN 957859-55Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.Proces

Strany 8

Publication 1757-RN508A-EN-P - October 20032 ProcessLogix R500.1 Service Pack 1 Contents of R500.1 SP1SP1 contains the following software

Strany 9

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 3Server Installation You must complete this procedure on all

Strany 10

Publication 1757-RN508A-EN-P - October 20034 ProcessLogix R500.1 Service Pack 1 12. At the Ready to Install window, click In stal l. Sta

Strany 11 - Known Problems in R500.1

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 5Client InstallationThe following steps can be used to insta

Strany 12

Publication 1757-RN508A-EN-P - October 20036 ProcessLogix R500.1 Service Pack 1 Manually Applying the Event Subsystem Updates1. Close all

Strany 13

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 7 16. Close the DOS window.17. Restart the PC.Problems Resol

Strany 14

Publication 1757-RN508A-EN-P - October 20038 ProcessLogix R500.1 Service Pack 1 42532 DNP3 History backfill does not fill the correct va

Strany 15

Publication 1757-RN508A-EN-P - October 2003ProcessLogix R500.1 Service Pack 1 9Client40128 OPC Data Server OPC Server allows writes befor